Generated from the same spec the renders and the 3D model are built
from, so they cannot drift from each other. Every dimension is millimetres.
01 · The bones
The room itself, and the water in it
Two sheets a joiner and a plumber both need and neither can get
from the cabinet drawings. The drawing figure is primary and the laser
reading sits under it — every laser reading so far has come in
slightly under, because drawing dimensions are struck to the frame while a
laser reads the finished plasterboard face. A reading 20–30mm under is a
confirmation, not a discrepancy, and it is drawn that way rather than as a
conflict. Every figure carries its provenance: WRITTEN off Sheet 3, MEASURED
by laser, CONFIRMED on site, or UNKNOWN — and the unknowns are
drawn as unknown rather than guessed. Three of them are what Monday’s
borescope exists to close.02 · Elevations
Fronts, and how tall everything is
The island is drawn as you see it from the walkway. The back run is
mirrored, so the fridge sits on the right where it actually is, rather than where
the coordinate system puts it. Every height is dimensioned on the drawing itself
— deliberately not repeated here, because prose and drawings drift apart and
the drawing is the one generated from the spec.03 · Plan
The island as it now stands
Every number is drawn from spec/kitchen.toml —
nothing on this sheet is typed by hand, so it cannot disagree with the model.
Red is under a standard or in dispute; green is resolved.
The island is a plain island — no seating, no knee overhang.
Working side facing the back run, left to right: drawers 1050, bin 450,
sink 800, dishwasher 600 — 2900, all standard 50mm modules. Table
side: three cupboards at 450 deep, each double-doored, because 900 and
1000 are both past the 600 single-leaf maximum and a leaf that wide swings its
own width into the dining area.
There is no separate Zip bay. The unit is drawn under the sink, which
is why the sink bay is 800 and not 600: an 800 gives 764 internal, and after
339 for the unit, 50 of inlet clearance and 105 for the CO2
cylinder that leaves 270 for the trap and waste. A 600 bay leaves 70 and was
never credible. Whether it can stay there is the one open question on the
whole layout — see the clearance note below.
The grey bands top and bottom are the fronts, ticked at every reveal
— what you will actually see. The six table-side fronts do not line
up with the seven on the working side, and the nearest pair miss by 50mm.
That is normally the exact distance that reads as a mistake rather than a
decision — but these are opposite faces of a free-standing island. You
cannot see both at once, and the only place they meet is the two ends, where
both faces do terminate together. Making them agree would mean giving up
symmetry, because the working side is not symmetric about the island’s
centre and never can be: the dishwasher and the bin decide it.
Two figures are derived, not given: the table-side cupboard widths
(three cupboards specified, no widths — 1000 + 900 + 1000 keeps
the odd bay in the middle so the six fronts read symmetrically), and the west
end sits 55mm proud of the wall face, which is what buys a standard 1050
drawer bank and a 932 east gap at the same time.
Slab. 3020 × 1110 — a 2700 cabinet box with a 300mm overhang at
the west end and 20mm at the east, 30mm each long face. One piece, inside a
standard slab.04 · The top band · whether
Do the doors run to the ceiling, or stop short?
Both are rendered from the same spec, so the only thing that
differs between them is the thing being argued about.
Above roughly 2080 you need a ladder, so a door up there is pretending to be
storage. B, which is what is specced, stops the doors at 2340 and runs one
sealed panel the remaining 140 to the ceiling: no handle, no hinge, one
horizontal line across the wall. If the hood recirculates, the void behind that
panel is the plenum and the discharge grille goes in it.
A third arrangement is not drawn: overheads stopping with bare painted
wall above — no panel, no joinery. It is the cheaper build and the default
a quote will assume unless it is specified otherwise. It is excluded here, and
named only so it is not arrived at by omission.
B is specified, and the 2340 standard is what makes it winnable. On
their 2160 standard the strip above the overheads is 320mm — a real band of
painted wall, the thing that makes a kitchen look fitted-into a room rather than
built-for it, and it collects dust you need a ladder to reach. At 2340 it is only
140, which is a much smaller panel to ask them for and a much smaller loss if they
refuse. That is the trade: 2340 buys 184mm of extra cupboard per bay and costs you
most of the band you were going to argue about.
Which of A and B is available still depends on the borescope: if the
existing hood is already ducted, the void behind B has no job and B becomes
purely a look.
These are working drawings, not construction drawings.
Dimensions come from the measured survey and the appliance manuals, and the model
is validated against them on every change — but a joiner measures the room
himself after demolition, and the 29mm scribe filler at the east end is the
piece that absorbs whatever the installer finds. It is drawn, scheduled and cut on site. Anything involving water, gas or a new circuit is
licensed trade work and is labelled as such in the schedules.